Coil data | ? |
---|---|
Rated coil voltage | 12/24/48/110 V DC, 12/24/110/230 V AC |
Rated voltage frequency | 50/60 Hz (AC) |
Coil power | DC: 0.53 W, AC: 1.2 VA |
Response voltage | AC:≤80%, DC: ≤75% |
Drop out voltage | AC: ≥30%, DC: ≥10% |
Operation time / Release time | Less than 20 ms / less than 10 ms (without diode) or 20 ms (with diode) |
Contact data | ? |
Contact numbers | 1 C/O |
Contact material | Ag alloy |
Rated voltage | 250 V AC |
Min. switching voltage | 5 V DC |
Max. switching voltage | 250 V AC, 30 V DC |
Rated current | 12 A |
Min. switching current | 100 mA / 5 V DC |
Max. inrush current | – |
Contact resistence | ≤ 50 mΩ (1 A/6 V DC) |
Mechanical service life | 1×107 times |
Electrical Service life (AC1) | 1×105 times |
General data | ? |
Rated withstand impulse voltage (Coil / Contact) | 5 kV AC / 1 min |
Rated withstand impulse voltage (Between contacts) | 1 kV AC / 1 min |
Surge voltage | 6 kV AC (1.2/50 μs) |
Insulation Resistance | 1,000 MΩ (500 V DC) |
Vibration | Malfunction 10~55 Hz (Amplitude 1.5 mm); Endurance? 10~55 Hz (Amplitude 1.5 mm) |
Shock | Malfunction 98 m/s2, Endurance 980 m/s2 |
Ambient temperature (Operation) | -40~70℃ |
Adapted Socket | SRE-1… |
Model designation | Number of poles | Coil voltage | AC/DC | Test Button | Build-in protective circuit | Special request |
RMIE | -2 | 24 | D | T | L | -XXX |
RMIE: Narrow version relay |
1: 1 C/O | 06: 06 V | D: DC | Blank: Standard | Blank: Standard | Special type or custom code, consisting of 3 digits letters combination |
2: 2 C/O | 12: 12 V | A: AC | T: With test button | L: LED | ||
3: 3 C/O | 24: 24 V | D: Diode | ||||
4: 4 C/O | 48: 48 V | RC: RC | ||||
60: 60 V | LD: LED + Diode | |||||
110: 110 V | LRC: LED + RC | |||||
220: 220 V | ||||||
230: 230 V |
Product manual - Interface Relay | Version 4.0 | 6 MB |
Coil data | ? |
---|---|
Rated coil voltage | 6/12/24 V DC |
Rated voltage frequency | – |
Coil power | DC: 0.4 W |
Response voltage | ≤75% (Room temp.) |
Drop out voltage | ≥5% (Room temp.) |
Operation time / Release time | Less than 20 ms / 10 ms |
Contact data | ? |
Contact numbers | 1 C/O |
Contact material | Ag alloy |
Rated voltage | 250 V AC |
Min. switching voltage | 5 V DC |
Max. switching voltage | 277 V AC, 30 V DC |
Rated current | 16 A |
Min. switching current | 100 mA / 5 V DC |
Max. inrush current | – |
Contact resistence | < 50 mΩ (1 A/6 V DC) |
Mechanical service life | 1×107 times |
Electrical Service life (AC1) | 1×105 times |
General data | ? |
Rated withstand impulse voltage (Coil / Contact) | 5 kV AC / 1 min |
Rated withstand impulse voltage (Between contacts) | 1 kV AC / 1 min |
Surge voltage | 8 kV AC (1.2/50 μs) |
Insulation Resistance | 1,000 MΩ (500 V DC) |
Vibration | Malfunction 10~55 Hz (Amplitude 1.5 mm); Endurance? 10~55 Hz (Amplitude 1.5 mm) |
Shock | Malfunction 98 m/s2, Endurance 980 m/s2 |
Ambient temperature (Operation) | -40~85℃ |
Adapted Socket | SRB-1… |
Model designation | Number of poles | Coil voltage | AC/DC | Special code | Special request |
RB | -1 | 24 | D | 3 | -XXX |
RB: Protective relay |
1: 1 C/O | 6: 6 V | D: DC | 3: Special for RB 1C | Special type or custom code, consisting of 3 digits letters combination |
2: 2 C/O | 12: 12 V | 6: Special for RB 2C | |||
24: 24 V |
Product manual - Interface Relay | Version 4.0 | 6 MB |
Coil data | |
---|---|
Rated coil voltage | 12/24/48/60 DC |
Rated voltage frequency | – |
Coil power | 0.217 W (48 V DC) |
Response voltage | ≤70% (Room temp.) |
Drop out voltage | ≥5% (Room temp.) |
Operation time / Release time | Less than 8 ms / Less than 4 ms |
Contact data | |
Contact numbers | 1 C/O |
Contact material | Ag alloy |
Rated voltage | 250 V AC |
Min. switching voltage | 5 V DC |
Max. switching voltage | 250 V AC, 30 V DC |
Rated current | 6 A |
Min. switching current | 100 mA / 5 V DC |
Max. inrush current | – |
Contact resistence | < 50 mΩ (1 A/6 V DC) |
Mechanical service life | 1×107 times |
Electrical Service life (AC1) | 1×105 times |
General data | |
Rated withstand impulse voltage (Coil / Contact) | 4 kV AC / 1 min |
Rated withstand impulse voltage (Between contacts) | 1 kV AC / 1 min (same contact group), 1.5 kV AC / 1 min (different contact group) |
Surge voltage | 6 kV AC (1.2/50 μs) |
Insulation Resistance | 1,000 MΩ (500 V DC) |
Vibration | Malfunction 10~55 Hz (Amplitude 1.5 mm); Endurance? 10~55 Hz (Amplitude 1.5 mm) |
Shock | Malfunction 98 m/s2, Endurance 980 m/s2 |
Ambient temperature (Operation) | -40~55℃ |
Adapted Socket | SRY-1… |
Model designation | Number of poles | Coil voltage | AC/DC | Test Button | Build-in protective circuit | Special request |
RY | -2 | 24 | D | T | L | -XXX |
RY: Slim relay |
1: 1 C/O | 06: 06 V | D: DC | Blank: Standard | Blank: Standard | Special type or custom code, consisting of 3 digits letters combination |
2: 2 C/O | 12: 12 V | A: AC | T: With test button | L: LED | ||
3: 3 C/O | 24: 24 V | D: Diode | ||||
4: 4 C/O | 48: 48 V | RC: RC | ||||
60: 60 V | LD: LED + Diode | |||||
110: 110 V | LRC: LED + RC | |||||
220: 220 V | ||||||
230: 230 V |