小说网,小说排行榜,有声小说 http://exas.com.cn Sun, 28 Oct 2018 09:38:39 +0000 en-US hourly 1 http://exas.com.cn/wp-content/uploads/2023/12/cropped-WRG1176x1176-透明-32x32.png Class II – WRG http://exas.com.cn 32 32 FIIR 160/385 (3+1) http://exas.com.cn/en/archives/product-items/fiir-160-385-31-en Sun, 28 Oct 2018 09:38:39 +0000 http://exas.com.cn/?post_type=avada_portfolio&p=14498 ? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

The post FIIR 160/385 (3+1) appeared first on WRG.

]]>

FIIR 160/385 (3+1)

? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

Electrical data
Category IEC / EN / VDE Class II / Type 2 / C
Max. continuous operating voltage (AC/DC)? Uc (L-N) 385/500 V
Max. continuous operating voltage (AC/DC)? Uc (N-PE) 255 V
Nominal discharge current (8/20) In 20 kA/20 kA
Max. discharge current (8/20) Imax 40 kA/40 kA
Voltage protection level Up (L-N) < 1.9 kV
Voltage protection level Up (N-PE) < 1.5 kV
Residual voltage Ures @ 5kA(8/20) < 1.4 kV
Follow current Ifi 100 ARMS
Response time tA < 25 ns / 100 ns
Thermal protection YES
Back-up fuse (if mains > 250 A) 125 Agl
Short-circuit withstand ISCCR 25 kA/50 Hz
General Data
Operating temperature -40 ~ 80℃
Terminal screw torque max. 3.0 Nm
Terminal cross section 35 mm2?(solid) / 25 mm2?(stranded)
Mounting 35 mm DIN rail, EN 60715
Protection degree IP20
Housing material Thermoplastic; inflammability class UL 94 V-0
Indication of disconnector operation red flag
Remote contacts (RC) YES
Remote contact ratings AC: 250 V/0.5 A, 125 V/3 A
Remote terminal cross section max. 1.5 mm2
Remote terminal torque 0.25 Nm
Standard IEC/EN 61643-11
Network systems TT, TN-S
Protection mode L-N,N-PE

The post FIIR 160/385 (3+1) appeared first on WRG.

]]>
FIIR 160/385 (4+0) http://exas.com.cn/en/archives/product-items/fiir-160-385-40-en Sun, 28 Oct 2018 09:34:14 +0000 http://exas.com.cn/?post_type=avada_portfolio&p=14494 ? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

The post FIIR 160/385 (4+0) appeared first on WRG.

]]>

FIIR 160/385 (4+0)

? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

Electrical data
Category IEC / EN / VDE Class II / Type 2 / C
Max. continuous operating voltage (AC/DC)? Uc (L-N) 385/500 V
Max. continuous operating voltage (AC/DC)? Uc (N-PE)
Nominal discharge current (8/20) In 20 kA per pole
Max. discharge current (8/20) Imax 40 kA per pole
Voltage protection level Up (L-N) < 1.9 kV
Voltage protection level Up (N-PE)
Residual voltage Ures @ 5kA(8/20) < 1.4 kV
Follow current Ifi NO
Response time tA < 25 ns
Thermal protection YES
Back-up fuse (if mains > 250 A) 125 Agl
Short-circuit withstand ISCCR 25 kA/50 Hz
General Data
Operating temperature -40 ~ 80℃
Terminal screw torque max. 3.0 Nm
Terminal cross section 35 mm2?(solid) / 25 mm2?(stranded)
Mounting 35 mm DIN rail, EN 60715
Protection degree IP20
Housing material Thermoplastic; inflammability class UL 94 V-0
Indication of disconnector operation red flag
Remote contacts (RC) YES
Remote contact ratings AC: 250 V/0.5 A, 125 V/3 A
Remote terminal cross section max. 1.5 mm2
Remote terminal torque 0.25 Nm
Standard IEC/EN 61643-11
Network systems TN-S
Protection mode L/N-PE

The post FIIR 160/385 (4+0) appeared first on WRG.

]]>
FIIR 40/385 http://exas.com.cn/en/archives/product-items/fiir-40-385-en Sun, 28 Oct 2018 09:28:40 +0000 http://exas.com.cn/?post_type=avada_portfolio&p=14490 ? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

The post FIIR 40/385 appeared first on WRG.

]]>

FIIR 40/385

? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

Electrical data
Category IEC / EN / VDE Class II / Type 2 / C
Max. continuous operating voltage (AC/DC)? Uc (L-N) 385/500 V
Max. continuous operating voltage (AC/DC)? Uc (N-PE)
Nominal discharge current (8/20) In 20 kA per pole
Max. discharge current (8/20) Imax 40 kA per pole
Voltage protection level Up (L-N) < 1.9 kV
Voltage protection level Up (N-PE)
Residual voltage Ures @ 5kA(8/20) < 1.4 kV
Follow current Ifi NO
Response time tA < 25 ns
Thermal protection YES
Back-up fuse (if mains > 250 A) 125 Agl
Short-circuit withstand ISCCR 25 kA/50 Hz
General Data
Operating temperature -40 ~ 80℃
Terminal screw torque max. 3.0 Nm
Terminal cross section 35 mm2?(solid) / 25 mm2?(stranded)
Mounting 35 mm DIN rail, EN 60715
Protection degree IP20
Housing material Thermoplastic; inflammability class UL 94 V-0
Indication of disconnector operation red flag
Remote contacts (RC) YES
Remote contact ratings AC: 250 V/0.5 A, 125 V/3 A
Remote terminal cross section max. 1.5 mm2
Remote terminal torque 0.25 Nm
Standard IEC/EN 61643-11
Network systems TN-S, TT, IT
Protection mode L/N-PE

The post FIIR 40/385 appeared first on WRG.

]]>
FIIR 80/385 (1+1) http://exas.com.cn/en/archives/product-items/fiir-80-385-11-en Sun, 28 Oct 2018 09:36:45 +0000 http://exas.com.cn/?post_type=avada_portfolio&p=14496 ? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

The post FIIR 80/385 (1+1) appeared first on WRG.

]]>

FIIR 80/385 (1+1)

? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

Electrical data
Category IEC / EN / VDE Class II / Type 2 / C
Max. continuous operating voltage (AC/DC)? Uc (L-N) 385/500 V
Max. continuous operating voltage (AC/DC)? Uc (N-PE) 255 V
Nominal discharge current (8/20) In 20 kA/20 kA
Max. discharge current (8/20) Imax 40 kA/40 kA
Voltage protection level Up (L-N) < 1.9 kV
Voltage protection level Up (N-PE) < 1.5 kV
Residual voltage Ures @ 5kA(8/20) < 1.4 kV
Follow current Ifi 100 ARMS
Response time tA < 25 ns / 100 ns
Thermal protection YES
Back-up fuse (if mains > 250 A) 125 Agl
Short-circuit withstand ISCCR 25 kA/50 Hz
General Data
Operating temperature -40 ~ 80℃
Terminal screw torque max. 3.0 Nm
Terminal cross section 35 mm2?(solid) / 25 mm2?(stranded)
Mounting 35 mm DIN rail, EN 60715
Protection degree IP20
Housing material Thermoplastic; inflammability class UL 94 V-0
Indication of disconnector operation red flag
Remote contacts (RC) YES
Remote contact ratings AC: 250 V/0.5 A, 125 V/3 A
Remote terminal cross section max. 1.5 mm2
Remote terminal torque 0.25 Nm
Standard IEC/EN 61643-11
Network systems TT, TN-S
Protection mode L-N,N-PE

The post FIIR 80/385 (1+1) appeared first on WRG.

]]>
FIIR 80/385 (2+0) http://exas.com.cn/en/archives/product-items/fiir-80-385-20-en Sun, 28 Oct 2018 09:32:17 +0000 http://exas.com.cn/?post_type=avada_portfolio&p=14492 ? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

The post FIIR 80/385 (2+0) appeared first on WRG.

]]>

FIIR 80/385 (2+0)

? Modular design
? Designed for sub-distribution boards
? MOV or GDT protection elements made in Europe

Electrical data
Category IEC / EN / VDE Class II / Type 2 / C
Max. continuous operating voltage (AC/DC)? Uc (L-N) 385/500 V
Max. continuous operating voltage (AC/DC)? Uc (N-PE)
Nominal discharge current (8/20) In 20 kA per pole
Max. discharge current (8/20) Imax 40 kA per pole
Voltage protection level Up (L-N) < 1.9 kV
Voltage protection level Up (N-PE)
Residual voltage Ures @ 5kA(8/20) < 1.4 kV
Follow current Ifi NO
Response time tA < 25 ns
Thermal protection YES
Back-up fuse (if mains > 250 A) 125 Agl
Short-circuit withstand ISCCR 25 kA/50 Hz
General Data
Operating temperature -40 ~ 80℃
Terminal screw torque max. 3.0 Nm
Terminal cross section 35 mm2?(solid) / 25 mm2?(stranded)
Mounting 35 mm DIN rail, EN 60715
Protection degree IP20
Housing material Thermoplastic; inflammability class UL 94 V-0
Indication of disconnector operation red flag
Remote contacts (RC) YES
Remote contact ratings AC: 250 V/0.5 A, 125 V/3 A
Remote terminal cross section max. 1.5 mm2
Remote terminal torque 0.25 Nm
Standard IEC/EN 61643-11
Network systems TN-S
Protection mode L/N-PE

The post FIIR 80/385 (2+0) appeared first on WRG.

]]>